Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Still deciding? Get samples of US$ 680/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
• Three phase in and single phase out design
It is realized to convert three-phase electrical to single-phase electrical output, reduce the load
capacity of each phase of input and the impact on the imbalance of the power grid, and improve
the load capacity of single-phase
• Strong load and overload capacity
Suitable for environments with a large load or insufficient single-phase load capacity
• Advanced DSP technology
Fast reaction speed, short response time, high control accuracy, high integration, environment-friendly
SpecificationModel | DPH31 10K-S | DPH31 15K-S | DPH31 20K-S | ||||
Phase | Three phase in /Single phase out | ||||||
Input | Rate capacity | 10KVA/800W | 15KVA/12KW | 20KVA/16KW | |||
Rate voltage | 400Vac(three phase with ground) | ||||||
Turn on voltage | 190-520Vac(three phase) ≤50% load | ||||||
305-520Vac(three phase) ≤100% load | |||||||
Frequency range | 46~54Hz or 56~64Hz | ||||||
Output | Rate voltage | 220/230/240Vac | |||||
Voltage regulation | ±1% | ||||||
Line mode frequency | 46~54Hz or 56~64Hz | ||||||
Bat mode frequency | 50Hz or 60Hz | ||||||
Harmonic | ≤3% linear load; ≤5% non-linear load | ||||||
Crest ration | 3:1 | ||||||
Transfer | 0ms | ||||||
Overload | 105%±5%<load≤125%±5%: 1min; 125%±5%< load ≤150%±5%: 30s; load>150%±5%: 300ms; ( transfer to bypass and alarm) | ||||||
Efficiency | Line mode | > 91% | |||||
BAT mode | > 91% | ||||||
BAT | Number | 16/20 | |||||
Charge voltage | 218.4V/273V | ||||||
Charge current (stand) | 1A/2A/4A adjustable,default 1A | ||||||
Charge current (long) | 1A/2A/4A adjustable,default 4A | ||||||
Size (D*W*H mm) | Stand UPS | 442*190*688 | No | ||||
Longtime UPS | 442*190*318 | 575*190*318 | |||||
Weight (kg) | Stand UPS | 66/76 | 68/78 | No | |||
Longtime UPS | 15 | 16 | 19 | ||||
Environment | Audible noise | ≤60dB | |||||
Temperature / Humidity | 0ºC~40ºC;20%~95% | ||||||
Communication | RS-232/USB/SNMP card |